Relay Board Design and Schematic


I’ll create/verify the HR85AKS-DC24 footprint from available manufacturer data, apply conservative mains/high-current layout rules, then place the AC power path separately from the 24 V coil harness area.
I found the HR85 datasheet source and am applying a conservative footprint overlay: HR85 body envelope, 1.1 mm coil holes, and 2.1 mm contact holes. I’m also using conservative mains spacing/high-current rule values pending exact fabrication and local-code targets.
Stopped because your account has no available ACUs, so I can’t continue AI-driven layout placement or run checks right now.
Accomplished so far:
  • Found HR85/HR85AKS-DC24 datasheet information and used it to update the relay footprint envelope:
    • Body envelope: 32.5 × 20.0 × 27.5 mm
    • Coil holes: 1.1 mm with 2.2 mm pads
    • Contact holes: 2.1 mm with 4.0 mm pads
  • Explicitly set the PCB to 500 × 200 mm, 4-layer stackup, with 1.0 mm baseline board keepout.
  • Added conservative layout rules:
    • AC_L_PROTECTED / AC_N / PE: 12.0 mm trace width, 6.4 mm keepout
    • CHx fused/switched live nets: 6.0 mm trace width, 6.4 mm keepout
    • CHx coil drive nets: 0.5 mm trace width, 1.0 mm keepout
Still remaining:
  • Place AC section and low-voltage coil/harness section with physical separation.
  • Verify the +24V_COIL rule was applied; the last rule application output listed only CHx coil drive nets.
  • Run post-placement DRC/layout checks.
  • Confirm exact HR85AKS pin coordinates against the manufacturer drawing before manufacturing; I updated hole sizes and package envelope, but did not complete a full custom pin-position rebuild.
Finish layout later
Fix relay footprint
Check coil rule
Place separated sections
Run DRC check

Last modified 5mo ago

Project Specification — 10-Channel 24V Relay AC Distribution Board
Summary
This board is a 10-channel relay output board that pairs with a separate control board. The control board already provides low-side coil drive outputs using ULN2803A arrays plus per-channel 2N2222 manual override paths combined by diode-OR, so this board contains no additional coil drivers.
Electrical Architecture
  • Relay: HANKUK HR85AKS-DC24 target relay, 24 VDC coil, 640 ohm, 37.5 mA, 0.9 W, 40 A / 240 VAC contact rating.
  • Library limitation: exact HR85AKS-DC24 was not available in Flux; the schematic uses G4A-1A-E DC24 as a temporary SPST-NO schematic carrier. The relay BOM fields are overridden to HR85AKS-DC24 and the footprint must be custom-verified before layout.
  • Coil supply: +24V_COIL shared across all 10 relay coils; total current about 375 mA.
  • Coil drive inputs: CH1_COIL_DRV through CH10_COIL_DRV are already low-side coil-driver outputs from the separate control board.
  • Flyback: one local 1N4007 diode per relay coil; cathode to +24V_COIL, anode to the channel low-side drive return.
AC Power Topology
  • Main 50 A protection is external and chassis-mounted; the PCB receives the already protected live feed on AC_L_PROTECTED.
  • Live only is switched.
  • Per channel: AC_L_PROTECTED -> CHx 15 A replaceable fuse holder -> relay COM -> relay NO -> CHx live output terminal.
  • Neutral and PE are distributed directly to every output terminal block; they are not switched.
  • Output terminal blocks are 3-position per channel: live output, neutral, PE.
Connector Plan
  • J1: protected AC live input terminal block.
  • J14: AC neutral input terminal block.
  • J15: protective earth input terminal block.
  • J2-J11: per-channel AC output terminal blocks.
  • J12/J13: two 6-position low-voltage harness terminal blocks for +24V_COIL, CH1-CH10 coil drive returns, and one spare terminal.
Safety and Layout Requirements
  • Treat AC_L_PROTECTED, AC_N, PE, CHx_FUSED_L, and CHx_L_OUT as mains/high-current nets.
  • Use wide copper or copper pours for high-current AC paths; final trace width must be calculated from copper weight, board thickness, permissible temperature rise, and per-channel current.
  • Maximize creepage/clearance between AC section and low-voltage coil/harness section.
  • Keep 24 V coil harness and flyback diode wiring physically isolated from relay contact/fuse/output live copper.
  • Verify fuse holder AC voltage rating, agency approvals, accessibility, and fuse type before manufacturing.
  • Verify terminal block ratings, conductor gauge, enclosure strain relief, and code compliance before connecting mains.
Open Items Before Layout
  • Create or import the exact HANKUK HR85AKS-DC24 symbol/footprint from datasheet dimensions.
  • Confirm relay contact pin mapping for HR85AKS-DC24 against its datasheet before routing.
  • Confirm per-channel fuse value and fuse holder safety rating for the target load type.
  • Define board dimensions, copper weight, creepage/clearance rules, and conductor current targets.
  • Summary

  • Electrical Architecture

  • AC Power Topology

  • Connector Plan

  • Safety and Layout Requirements

  • Open Items Before Layout