Induction Heater Layout


A 5 A fuse can be used temporarily, but 4 A is safer and preferred for this ~3 A / 72 W design.
A 5 A fuse does not limit normal current to 5 A; depending on its time-current curve, it may carry substantially more than 5 A for seconds or minutes. That reduces protection for the perfboard wiring, chokes, MOSFETs, connectors, and supply.
If using the 5 A fuse:
  • Use it only if the supply itself has a reliable 3 A current limit.
  • Ensure the fuse is rated for at least 32 VDC; an automotive blade fuse is suitable for 24 V DC.
  • Use 14–16 AWG input wiring and heavy copper buses.
  • Do not increase the supply current above 3 A merely because the fuse is 5 A.
  • Fit the fuse in the +24 V input, close to the connector.
  • Replace it with a 4 A time-delay fuse when available.
For initial tests, set the bench supply to 0.5–1 A, verify stable oscillation, and then increase gradually toward 3 A. If your power supply cannot current-limit, I would not recommend powering this build with the 5 A fuse alone.
E102 20Kv is this ceramic cap to large to substitute C3???
No. 102 means 1,000 pF = 1 nF = 0.001 µF. C3 requires 100 nF = 0.1 µF, normally marked 104.
Therefore, the E102 is 100× too small in capacitance. Its 20 kV rating is harmless electrically but unnecessary, and the part may be physically large with long leads—poor for high-frequency bypassing.
For C3, look for:
  • Marking: 104
  • Capacitance: 100 nF / 0.1 µF
  • Voltage: 50 V minimum; 100 V preferred
  • Type: ceramic disc or small film
  • Mount with the leads as short as possible
The required part may say 104, 104K, 104Z, 0.1uF, or 100nF.

Perfboard Wiring Verification
Focused readability correction — 2026-09-20
Readability assessment: credible as a zoomable assembly-reference map when used with the terminal table below. This is an engineering visual assessment, not a novice usability test or full-power safety release. The final rendered layout was inspected after moving clipped/overlapping callouts and replacing crowded component references.

Table


Correction itemStatusResult
Preserve placement and 16-net connectivityCompletedOnly text, annotation leaders/circles, and text-only layout rules changed. No traces, vias, pads, components, schematic nets, values, or board geometry changed in this pass.
Do not use CAD red/blue as polarityCompletedCentral legend states CAD colors are layers, not polarity. Explicit +24V POWER, GND / 0V, CONTROL SIGNAL, UNDERSIDE INSULATED LINK and HEAVY COPPER BUS wording identifies construction/function.
Label J1–J4 terminalsCompletedPin-specific callouts and leaders identify J1 supply polarity, J2 HEATER+/HEATER-, J3 thermal-loop terminals, and J4 COIL_A/COIL_B; adjacent J4 tags read 1:A and 2:B. J2 HEATER- is explicitly NOT GND.
Heavy current pathsCompletedB01/B02 identify the separate drain–tank–coil heavy copper/braid paths; B03 identifies the top source-return heavy bus and GND / 0V backbone. P01/P02 identify heavy-rated positive power wiring, not standard perfboard tracks.
Physical sides and crossing insulationCompletedTOP means component side and BOTTOM means underside. B01/B02 are underside buses except the B02 J4.2–C4.2 top jumper. B03 source backbone is top-mounted. P01/P02 main supply links and the labeled P03 control branch are underside insulated links. X1 and X2 explicitly identify high-risk crossings; all different-net crossings must remain separated/insulated.
Legend and label overlap cleanupCompletedReplaced the old scattered legend; moved terminal captions inside the board; split long captions; removed crowded source-footprint text only and replaced it with unique nearby references. Values remain in the schematic/BOM and the connection table. Thin cyan leaders are explicitly annotation pointers, not additional wires.
Numbered identifiersCompleted as route-group IDsP01–P03, B01–B03 and S01–S10 cross-reference the table below. These identify nets/route groups, not individual precut wire lengths.
Fresh airwire/redundant checksCompletedFinal routing-state inspection: 0 airwires, 0 redundant traces. Fresh airwire/redundant DRC query returned no findings; the preceding full DRC/placement error-warning query also returned no findings.
BOARD_DEFINITION_GENERIC diagnosisUnattempted in this annotation-only pass; unresolved limitation retainedThe earlier routing-engine anomaly is neither proof that this wiring map fails nor proof that it succeeds. No claim of resolving it is made.
Novice user test, actual wire sizing, physical assembly and full-power validationUnattempted / outside this correction passContinue the existing physical verification and staged bring-up precautions.
Numbered route-group cross-reference
Use the complete net-to-terminal table later in this file for every solder endpoint. Do not join different IDs together merely because their drawn paths cross.

Table


IDExisting netConstruction/function
P01VIN+J1.1 to F1.1; underside insulated, heavy-rated +24V power wire; red insulation.
P02VIN_FUSEDF1.2 to L1:P1/L2:P1 and protected supply branches; main distribution is underside insulated heavy-rated +24V wiring; red insulation. Bias/bypass branches retain their displayed sides.
P03GATE_BIASQ3:C to R4:P1/R5:P1; switched-positive low-current wire, red insulation. Q3–R4 branch is underside; R4–R5 branch is top.
B01COIL_AQ1 drain to L1:P2, capacitor pin-1 column and J4.1/direct coil A; underside heavy copper/braid bus. D4 cathode connection is an insulated blue control branch, not resonant-current braid.
B02COIL_BQ2 drain to L2:P2, capacitor pin-2 column and J4.2/direct coil B; underside heavy copper/braid bus, except the J4.2–C4.2 link is top-mounted. D3 cathode is an insulated blue control branch.
B03VIN-Top-mounted MOSFET source-return heavy copper/braid backbone; GND / 0V. Use black insulation on insulated return wires; local low-current branches retain displayed sides.
S01HEATER+J2.1 command-input positive to R1; red insulation, not an internal connection to P01.
S02HEATER-J2.2 command-input negative to U1/D1; black insulation; not B03/GND.
S03HEAT_LED_AR1/U1/D1 LED-anode control wiring; underside blue insulated links.
S04THERMAL_SWJ3.1 to R3; blue control wire for external normally-closed thermal switch.
S05THERMAL_SW_RETURNJ3.2 to U1:4; underside blue insulated control link, not GND.
S06ENABLE_BASEQ3 base/R2/R3 enable node; blue control wiring.
S07GATE_DRV_AR4/D3/R6 gate-drive group; blue insulated control wiring.
S08GATE_DRV_BR5/D4/R7 gate-drive group; blue insulated control wiring.
S09GATE_Q1R6/Q1 gate/R8/D5 clamp; short local blue gate wiring.
S10GATE_Q2R7/Q2 gate/R9/D6 clamp; short local blue gate wiring.
Crossing markers and orientation
  • X1, near board coordinates (+5.31, -12.03) mm: B01 underside coil-A link crosses the B02 top coil-B jumper. Keep the two buses physically separated and sleeve/insulate against accidental contact. No solder joint here.
  • X2, near (-22.86, -23.59) mm: the P03 underside gate-bias wire passes beneath the top COIL_B-to-D3 cathode control branch. Use intact insulation; no solder joint here.
  • These are highlighted examples, not permission to leave other crossings bare. All different-net crossings, including top/underside overlaps elsewhere, require physical separation and appropriate insulation.
  • The map is viewed from the component side. When physically flipping the perfboard to solder underneath, left/right reverses. Confirm pins by the Jx.y labels and continuity, not color or visual left/right alone.
  • J4 has two alternating tank ends, not DC +/-. Its prototype-only limitation remains; do not assume its terminal block is suitable for full resonant current.
The following original routing verification and complete endpoint table remain applicable, except that novice-readability status is superseded by the correction assessment above.
Status and scope
This is an assembly wiring map, not an etched PCB design or a full-power construction release.

Table


Assigned itemStatusEvidence / remaining limitation
Preserve approved placement and outlineCompletedNo component position, rotation, footprint, schematic connection, or board-outline edits were made. Board remains 91.44 × 121.92 mm, 32 components.
Initial routing precheckCompletedPassed before adding links and again immediately before auto-routing: board valid, 32 components, 16 nets, no routing-feasibility issues.
Route every existing schematic netCompletedInitially 53 airwires. Explicit heavy links followed by one auto-route pass; final routing-state inspection reports 0 airwires, 0 redundant traces. No vias were generated.
Heavy bus topologyCompleted as an annotated wiring representationCOIL_A, COIL_B and the source-return backbone have explicit 2 mm-wide graphical links; positive input/feed backbones have 1.5 mm-wide links. These widths identify construction classes, NOT validated copper-wire diameters or etched-trace ampacity.
Airwire/DRC verificationCompletedFinal Design Rule Checks / Placement Checks query returned no ERROR or WARNING findings. One redundant auto-routed GATE_DRV_B segment was removed and connectivity rechecked.
Repeat routing-engine precheck after completionFailed / unresolvedReturns BOARD_DEFINITION_GENERIC: Board validation failed with errors, without a component, net, geometry, or actionable cause. This conflicts with clean DRC and complete routing. Targeted stackup/invalid-layer/invalid-pad/layout-cell-tree/system checks returned no explanatory findings. Do not call the project universally validation-clean. No speculative board or placement changes were made.
Literal red/black/blue copper displayUnattempted: unsupported by exposed routing rulesCAD copper remains colored by layer, not net. Added visible wire-color legend and explicit warning that CAD red/blue are layer colors. Native per-net insulation-color rendering is not established.
Full-power physical buildabilityUnattempted / not certifiedWire/braid cross-section, resonant RMS current, insulation spacing at physical crossings, perfboard lead forming, and thermal behavior are not validated by PCB DRC.
The electrical-routing batch is complete; the entire requested color-coded, physically validated novice-build release is not complete.
How to read the visible layout
  • Bottom copper represents underside point-to-point links. Top copper represents top-side jumpers/buses. No continuous copper planes or plated vias are required by this map.
  • Wide links are separate heavy copper wire, braid, or bus links, not rows of perfboard pads and not solder-bridged thin tracks. Solder directly to the appropriate component leads and mechanically secure the conductors.
  • A top/bottom crossing in CAD must remain electrically separated in the real build. Use suitable sleeving/insulation and physical spacing; a bare crossing is not permitted. The COIL_A and COIL_B links immediately below J4 cross on different represented sides.
  • CAD red means Top and CAD blue means Bottom in the inspected 2D view. Those colors do not specify physical wire insulation. Follow the wire-color table below.
  • The displayed board uses continuous physical coordinates. Existing footprints include pitches that are not exact multiples of 2.54 mm. Lead forming/adapter provisions are still required where appropriate; this is not a verified hole-by-hole perfboard drilling template.
  • View from the opposite side reverses left/right. Identify terminals by designator and pin, not by the screen position alone.
Heavy conductor paths

Table


Net / pathRequired construction class
COIL_A: Q1 drain (pin 2), L1:P2, C4:1, C5:1, C6:1, J4:1/direct coil end AHeavy bare copper or braid/bus; insulate and secure wherever it crosses another conductor. D4:K is a low-current, high-voltage-rated blue cross-coupling branch from this net, not part of the resonant-current conductor.
COIL_B: Q2 drain (pin 2), L2:P2, C4:2, C5:2, C6:2, J4:2/direct coil end BHeavy bare copper or braid/bus. D3:K is the corresponding blue insulated cross-coupling branch.
VIN-: Q1 source (pin 3) to Q2 source (pin 3), then power-input/bulk-capacitor returnHeavy source-return bus and suitably rated black insulated power-return wiring. Low-current gate-clamp, pull-down and U1 return branches may use black insulated signal wire.
VIN+: J1:1 to F1:1Red insulated power wire, sized for the fused input path; drawn wider than control connections.
VIN_FUSED: F1:2 to L1:P1 and L2:P1; bulk/bypass positive supplyRed insulated power distribution or heavy bus with red polarity identification. Q3/R2 bias branches are low-current red wiring.
Tank capacitor columns are joined directly, with short drain links to their respective MOSFETs. The fixed input/bulk-capacitor placement remains far from the MOSFET row; the relatively long DC feed/return routes are not evidence of minimum loop inductance. No component move is required to achieve connectivity, and none was made. Further power-loop optimization would be a separate approved placement task.
J4 remains prototype-only. Its existing project role explicitly states circulating-current suitability is unconfirmed. At full resonant current use properly rated direct coil-to-bus attachment rather than assuming this terminal block is sufficient. The map does not certify a particular wire gauge or braid size.
Complete net-to-terminal assembly table
Every terminal in each row must be electrically common, with no connection to any other row. MOSFET pin numbers below follow the existing project assignments: 1 gate, 2 drain, 3 source.

Table


NetPhysical wire color / classConnected terminals
VIN+Red powerJ1:1, F1:1
VIN_FUSEDRed power distribution; red low-current bias branchesF1:2, D2:C (cathode), C1:P1 (+), C2:P1, C3:P1, L1:P1, L2:P1, Q3:E, R2:P1
VIN-Black; heavy source/power return plus low-current branchesJ1:2, D2:A, C1:P2 (-), C2:P2, C3:P2, Q1:3, Q2:3, R8:P2, R9:P2, D5:A, D6:A, U1:3
COIL_AHeavy tank bus; blue insulated D4 cathode branchQ1:2, L1:P2, C4:1, C5:1, C6:1, J4:1, D4:K
COIL_BHeavy tank bus; blue insulated D3 cathode branchQ2:2, L2:P2, C4:2, C5:2, C6:2, J4:2, D3:K
GATE_BIASRed switched-positive low-current wireQ3:C, R4:P1, R5:P1
GATE_DRV_ABlueR4:P2, D3:A, R6:P1
GATE_DRV_BBlueR5:P2, D4:A, R7:P1
GATE_Q1Blue, short local gate wiringR6:P2, Q1:1, R8:P1, D5:K
GATE_Q2Blue, short local gate wiringR7:P2, Q2:1, R9:P1, D6:K
ENABLE_BASEBlueQ3:B, R2:P2, R3:P1
HEATER+Red command-input positive; NOT internally tied to VIN+J2:1, R1:P1
HEATER-Black command-input negative; NOT internally tied to VIN-J2:2, U1:2, D1:A
HEAT_LED_ABlueR1:P2, U1:1, D1:K
THERMAL_SWBlueJ3:1, R3:P2
THERMAL_SW_RETURNBlueJ3:2, U1:4
R4/R5 remain the existing 470 ohm enabled gate-bias resistors, R6/R7 the 10 ohm series resistors, R8/R9 the 10k pull-downs, and D5/D6 the existing 12 V clamps. No schematic values were changed. D3 and D4 connect each drive node to the opposite tank/drain node through their cathodes as listed above.
Before energizing
  1. Resolve or explain the final routing-engine BOARD_DEFINITION_GENERIC failure before relying on that engine for further modifications.
  2. Verify each row of the table by continuity and verify isolation between different rows with power disconnected. Confirm diode bands, capacitor polarity, MOSFET pins and heatsink electrical isolation against the actual purchased parts.
  3. Confirm actual component lead fit on the chosen perfboard, conductor cross-sections, mechanical support and insulation at every crossing. PCB DRC does not verify these assembly conditions.
  4. Confirm direct high-current coil attachments and suitable tank-capacitor ripple-current capability; retain the project's existing fuse, thermal interlock and bring-up precautions.
  5. Full-power operation requires current-limited staged testing and measurement of tank/drain waveforms and conductor/component temperature. Zero airwires is not a guarantee of safe operation.
  • Focused readability correction — 2026-09-20

  • Numbered route-group cross-reference

  • Crossing markers and orientation

  • Status and scope

  • How to read the visible layout

  • Heavy conductor paths

  • Complete net-to-terminal assembly table

  • Before energizing