O U LL Pinout and Electrical-Characterization Worksheet
Purpose
Determine the exact pin functions, connector orientation, voltage, current, load type, grounding, and isolation classification for legacy ports:
  • O: 2-position AC line-voltage connection
  • U: 2-position high-current auxiliary connection; function unknown
  • LL: 3-position auxiliary power/control connection; function unknown
No schematic connection, adapter wiring, or energized prototype connection is authorized until this worksheet is completed and independently reviewed.
Mandatory safety conditions
  • Treat every unknown pin as hazardous until proven otherwise.
  • Testing of energized or potentially mains-connected ports must be performed by a qualified person.
  • Use appropriately CAT-rated true-RMS instruments, insulated probes, PPE, barriers, strain relief, and an emergency disconnect.
  • Do not use continuity or resistance mode on an energized connector.
  • Before resistance testing, disconnect AC mains, batteries, backup supplies, capacitors, and every external cable that could backfeed the equipment.
  • Verify zero AC and DC voltage before touching conductors or changing meter modes.
  • Never measure prospective fault current by intentionally shorting pins.
  • Do not connect an earth-referenced oscilloscope to an unknown floating or mains-referenced circuit.
  • Stop testing if connector numbering, protective-earth relation, source isolation, or safe access is uncertain.
  • Port O must remain excluded from the low-voltage Bed Control Bench Prototype. If required, it belongs only in a separately enclosed hazardous-voltage interface.
Equipment record

Table


InstrumentManufacturer/modelSerialCAT / voltage ratingCurrent rangeCalibration due
True-RMS multimeter
AC/DC current clamp or power analyzer
Insulation-resistance tester
Isolated differential probe
Oscilloscope/data recorder
Temperature probe
Equipment-under-test record
  • Manufacturer: ________________________________________________
  • Model: _______________________________________________________
  • Serial number: _______________________________________________
  • Configuration/options installed: ______________________________
  • Supply source: _______________________________________________
  • Upstream breaker/fuse: _______________________________________
  • Test date: __________________ Technician: _____________________
  • Independent reviewer: ________________________________________
  • Ambient temperature: ______ °C
  • Altitude: ______ m
Connector-orientation procedure
For each connector:
  1. Photograph the mating face straight-on.
  2. Photograph the wire-entry/rear face straight-on.
  3. Record latch, key, polarization, and pin-1 markings.
  4. State which view defines the numbering used in this worksheet.
  5. Verify numbering with a second person before any energized measurement.
  6. Do not infer pin numbers from wire colors alone.

Port O — 2 Positions
O connector identification
  • Connector manufacturer/series: _______________________________
  • Housing MPN: __________________________________________________
  • Mating housing MPN: __________________________________________
  • Contact MPN and wire range: __________________________________
  • Number of positions: 2
  • Key/latch location: ___________________________________________
  • Pin-1 datum/mark: _____________________________________________
  • Numbering view:
    • Looking into equipment-side mating face
    • Looking into cable-side mating face
    • Looking into wire-entry face
  • Mating-face photo filename: __________________________________
  • Rear-face photo filename: ____________________________________
  • Orientation independently confirmed: [ ]
O de-energized continuity and resistance
Before testing:
  • AC cord disconnected: [ ]
  • Battery/backup source disconnected: [ ]
  • Stored energy discharged: [ ]
  • Zero voltage verified: [ ]

Table


MeasurementResistance/continuityNotes
O1 ↔ O2
O1 ↔ protective earth/chassis
O2 ↔ protective earth/chassis
O1 ↔ known line input
O2 ↔ known neutral input
O1 ↔ known transformer winding
O2 ↔ known transformer winding
O1 ↔ low-voltage common
O2 ↔ low-voltage common
O energized voltage characterization
Perform only if qualified and safe access is established.

Table


Operating stateO1–O2 VAC RMSO1–O2 VDCO1–earth VACO2–earth VACFrequencyPeak/transientNotes
Equipment powered, idle
Head UP
Head DOWN
Foot UP
Foot DOWN
Fowler UP
Fowler DOWN
Auxiliary functions active
O current and source characterization
  • Current through O1/O2 in idle: ______ A RMS
  • Maximum steady-state current: ______ A RMS
  • Maximum inrush/peak current: ______ A
  • Inrush duration: ______ ms
  • Power factor: ______
  • Real power: ______ W
  • Apparent power: ______ VA
  • Source classification:
    • Direct building mains
    • Isolated transformer secondary
    • Autotransformer/non-isolated derived source
    • Switched mains branch
    • Unknown — stop
  • Prospective fault current from approved documentation/method: ______ A
  • Upstream protective device: __________________________________
O derived pin assignment

Table


O positionProposed functionVoltage classCurrent classEarth/chassis relationConfidence
1[ ] LINE [ ] NEUTRAL [ ] Isolated AC [ ] Other ______ [ ] Unknown
2[ ] LINE [ ] NEUTRAL [ ] Isolated AC [ ] Other ______ [ ] Unknown
O isolation classification
  • Hazardous building-mains circuit
  • Hazardous isolated secondary
  • SELV/PELV
  • Functional extra-low voltage
  • Protective earth
  • Unknown — no design action allowed
O disposition:
  • Exclude from all PCB designs
  • Include only in separate enclosed 120 VAC interface
  • Requires separate power-entry/safety design
  • Blocked pending further testing

Port U — 2 Positions
U connector identification
  • Connector manufacturer/series: _______________________________
  • Housing MPN: __________________________________________________
  • Mating housing MPN: __________________________________________
  • Contact MPN/wire range: ______________________________________
  • Key/latch location: ___________________________________________
  • Pin-1 datum/mark: _____________________________________________
  • Numbering view: ______________________________________________
  • Mating-face photo filename: __________________________________
  • Rear-face photo filename: ____________________________________
  • Wire colors: U1 __________; U2 __________
  • Orientation independently confirmed: [ ]
U de-energized continuity matrix

Table


MeasurementResistance/continuityNotes
U1 ↔ U2
U1 ↔ protective earth/chassis
U2 ↔ protective earth/chassis
U1 ↔ AC line
U2 ↔ AC line
U1 ↔ AC neutral
U2 ↔ AC neutral
U1 ↔ +12 V supply
U2 ↔ +12 V supply
U1 ↔ low-voltage return
U2 ↔ low-voltage return
U1 ↔ motor/actuator winding
U2 ↔ motor/actuator winding
U voltage by operating state

Table


StateU1–U2 VAC RMSU1–U2 VDCU1–earth VAC/VDCU2–earth VAC/VDCFrequencyPolarityNotes
Equipment off
Powered, idle
Head motion
Foot motion
Fowler motion
Knee/Gatch motion
Auxiliary control activated
U current and inrush

Table


State/functionSteady currentPeak currentInrush durationDuty cyclePower factor/load typeNotes
Idle
Function 1
Function 2
Worst case
  • Prospective fault current/source limit: ______ A
  • Upstream fuse/breaker: ________________________________________
  • Minimum wire gauge observed: _________________________________
  • Connector/contact current rating: _____________________________
  • Temperature rise after ______ minutes: ______ °C
U functional investigation
Disconnect power and trace the harness/equipment wiring where safe.

Table


U positionDestination/componentObserved functionSource or load?Normally energized?Confidence
1
2
Possible classifications:
  • AC power source
  • DC power source
  • Motor/actuator output
  • Switched auxiliary load
  • Dry contact
  • Sensor/control input
  • Protective earth/chassis
  • Unknown
U derived assignment

Table


U positionFinal proposed nameDirectionNominal voltageMaximum current/inrushIsolation domainStatus
1[ ] Input [ ] Output [ ] Bidirectional[ ] Verified [ ] TBD
2[ ] Input [ ] Output [ ] Bidirectional[ ] Verified [ ] TBD
U disposition:
  • Safe for low-voltage controller PCB
  • Belongs only on separate hazardous/high-current module
  • Mechanical NC/DNP placeholder only
  • Exclude entirely
  • Blocked pending further testing

Port LL — 3 Positions
LL connector identification
  • Connector manufacturer/series: _______________________________
  • Housing MPN: __________________________________________________
  • Mating housing MPN: __________________________________________
  • Contact MPN/wire range: ______________________________________
  • Key/latch location: ___________________________________________
  • Pin-1 datum/mark: _____________________________________________
  • Numbering view: ______________________________________________
  • Mating-face photo filename: __________________________________
  • Rear-face photo filename: ____________________________________
  • Wire colors: LL1 ________; LL2 ________; LL3 ________
  • Orientation independently confirmed: [ ]
LL de-energized continuity matrix

Table


MeasurementResistance/continuityNotes
LL1 ↔ LL2
LL1 ↔ LL3
LL2 ↔ LL3
LL1 ↔ protective earth/chassis
LL2 ↔ protective earth/chassis
LL3 ↔ protective earth/chassis
LL1 ↔ AC line/neutral
LL2 ↔ AC line/neutral
LL3 ↔ AC line/neutral
LL1 ↔ +12 V / DC return
LL2 ↔ +12 V / DC return
LL3 ↔ +12 V / DC return
LL1 ↔ known control input/output
LL2 ↔ known control input/output
LL3 ↔ known control input/output
LL voltage by operating state

Table


StateLL1–LL2LL1–LL3LL2–LL3LL1–earthLL2–earthLL3–earthAC/DC/frequency notes
Equipment off
Powered, idle
Head motion
Foot motion
Fowler motion
Knee/Gatch motion
Auxiliary function
LL current and signal behavior
Measure current only with a safe, correctly inserted instrument or isolated current probe.

Table


Pin/pathIdle currentActive currentPeak/inrushDuty cycleSignal waveform/frequencyNotes
LL1
LL2
LL3
LL1–LL2 path
LL1–LL3 path
LL2–LL3 path
LL functional investigation

Table


LL positionDestination/componentProposed functionSource/load/controlNormal stateConfidence
1
2
3
Check all applicable classifications:
  • Supply positive/line
  • Supply return/neutral
  • Protective earth/shield
  • Switched output
  • Dry-contact common
  • Control input
  • Analog signal
  • Digital signal
  • Motor/actuator conductor
  • Unknown
LL derived assignment

Table


LL positionFinal proposed nameDirectionNominal voltageMaximum currentIsolation domainStatus
1[ ] Input [ ] Output [ ] Bidirectional[ ] Verified [ ] TBD
2[ ] Input [ ] Output [ ] Bidirectional[ ] Verified [ ] TBD
3[ ] Input [ ] Output [ ] Bidirectional[ ] Verified [ ] TBD
LL disposition:
  • Safe for low-voltage controller PCB
  • Belongs only on separate hazardous/high-current module
  • Mechanical NC/DNP placeholder only
  • Exclude entirely
  • Blocked pending further testing

Isolation and domain classification
Complete after individual-port measurements.

Table


BoundaryMeasured resistanceMeasured working voltageRequired insulation typeProposed project/domainPass/fail
O ↔ logic/SELV[ ] Functional [ ] Basic [ ] Reinforced
U ↔ logic/SELV[ ] Functional [ ] Basic [ ] Reinforced
LL ↔ logic/SELV[ ] Functional [ ] Basic [ ] Reinforced
O ↔ chassis/earth
U ↔ chassis/earth
LL ↔ chassis/earth
O ↔ existing 120 VAC N/G/CC interface
U ↔ existing 120 VAC N/G/CC interface
LL ↔ existing 120 VAC N/G/CC interface
Insulation-resistance testing
Do not perform megohmmeter or hipot testing until all connected electronics are reviewed for test-voltage tolerance and isolated/disconnected as required.
  • Approved test voltage: ______ VDC / VAC
  • Approval/reference: __________________________________________
  • Sensitive circuits disconnected: [ ]
  • Qualified test procedure attached: [ ]

Table


Test boundaryTest voltageDurationMeasured resistance/leakagePass criterionResult
O to SELV
U to SELV
LL to SELV
Stop conditions
Stop and leave the pin assignment as TBD if any condition applies:
  • Connector orientation or pin numbering is uncertain.
  • A pin has hazardous voltage not documented in the equipment service information.
  • A proposed low-voltage pin is connected to mains, protective earth, a motor winding, or a high-current source.
  • Current or inrush exceeds the instrument, connector, wire, or temporary protection rating.
  • A pin changes function with operating state in an unexplained way.
  • Fault-current information is unavailable for a proposed power connection.
  • Isolation cannot be classified as SELV, basic, or reinforced with evidence.
  • Measurement results conflict with continuity tracing or wire destinations.
  • U or LL remains described only as auxiliary without a demonstrated function.
Design-release summary

Table


PortConnector/pinout verifiedVoltage/current verifiedIsolation verifiedApproved destinationSchematic action
O[ ][ ][ ][ ] Separate HV module [ ] Exclude
U[ ][ ][ ][ ] Low-voltage PCB [ ] Separate HV module [ ] Exclude
LL[ ][ ][ ][ ] Low-voltage PCB [ ] Separate HV module [ ] Exclude
Final sign-off
  • Technician: __________________________________ Date: __________
  • Independent electrical reviewer: ______________ Date: __________
  • Safety reviewer: ______________________________ Date: __________
  • Photos and raw measurement files archived: [ ]
  • Manufacturer/service information attached: [ ]
  • Final connector orientation drawing attached: [ ]
  • Final status:
    • Approved for schematic update
    • Approved only as NC/DNP mechanical placeholders
    • Blocked pending additional investigation
  • O U LL Pinout and Electrical-Characterization Worksheet

  • Purpose

  • Mandatory safety conditions

  • Equipment record

  • Equipment-under-test record

  • Connector-orientation procedure

  • Port O — 2 Positions

  • O connector identification

  • O de-energized continuity and resistance

  • O energized voltage characterization

  • O current and source characterization

  • O derived pin assignment

  • O isolation classification

  • Port U — 2 Positions

  • U connector identification

  • U de-energized continuity matrix

  • U voltage by operating state

  • U current and inrush

  • U functional investigation

  • U derived assignment

  • Port LL — 3 Positions

  • LL connector identification

  • LL de-energized continuity matrix

  • LL voltage by operating state

  • LL current and signal behavior

  • LL functional investigation

  • LL derived assignment

  • Isolation and domain classification

  • Insulation-resistance testing

  • Stop conditions

  • Design-release summary

  • Final sign-off