SYSTEM interconnect schematic
Create the SYSTEM sheet with 12 hierarchical interconnect blocks and required callout
Add and verify named system nets and enclosure/off-sheet ports
Verify architecture locks and inventory all blocks, ports, and invented parts
SYSTEM functional group: 12 architecture blocks, 8 enclosure ports, 37 named nets, and the complete 12-line specification callout. The original 189-component concept remains untouched; all 21 new instances are excluded from PCB, BOM, and pick-and-place, and no PCB layout or high-power copper was created.GRID_PASSTHROUGH, SERVICE_CT, AC_INTERFACE, TTYPE_NPC, HV_DC_BUS, PV_MPPT, BATT_IF, MISC_IF, SENSE_PROT, CTRL_PCS, AUX_PSU, THERMAL.GRID_INPUT_200A, LOAD_OUTPUT_200A, SOLAR_PV_INPUT_15_20KW, BATTERY_BIDIRECTIONAL_15_20KW, MISC_DC_BIDIRECTIONAL_10_15KW, WHOLE_HOME_CT_INPUTS, COMMUNICATION_PORTS, GROUNDING_LUG.GRID_PASSTHROUGH_ARCH_MOCK, SERVICE_CT_ARCH_MOCK, AC_INTERFACE_ARCH_MOCK, TTYPE_NPC_ARCH_MOCK, HV_DC_BUS_ARCH_MOCK, PV_MPPT_ARCH_MOCK, BATT_IF_ARCH_MOCK, MISC_IF_ARCH_MOCK, SENSE_PROT_ARCH_MOCK, CTRL_PCS_ARCH_MOCK, AUX_PSU_ARCH_MOCK, THERMAL_ARCH_MOCK, SPLIT_PHASE_200A_ENCLOSURE_PORT_ARCH_MOCK, PV_ENCLOSURE_PORT_ARCH_MOCK, BATTERY_ENCLOSURE_PORT_ARCH_MOCK, MISC_DC_ENCLOSURE_PORT_ARCH_MOCK, WHOLE_HOME_CT_ENCLOSURE_PORT_ARCH_MOCK, COMMUNICATION_ENCLOSURE_PORT_ARCH_MOCK, GROUNDING_LUG_ARCH_MOCK, SYSTEM_SPEC_CALLOUT_ARCH_MOCK.SYSTEM is isolated as a functional group in a separate canvas region rather than a physical sheet tab; the existing concept could not be renamed CONCEPT-DO-NOT-LAYOUT. Full connectivity evidence and the net inventory are recorded in system-architecture-implementation-report.Table
| Criterion | 2-level full bridge | 3-level T-type NPC | 3-level NPC / ANPC |
|---|---|---|---|
| Device blocking stress | Each active device must withstand full DC bus plus overshoot; 1200 V SiC is natural for 800 V bus | Outer path must tolerate fault/commutation stress; 1200 V SiC provides margin even though nominal steps are half-bus | Similar half-bus nominal steps; clamping devices and fault states require careful full-bus analysis |
| Switching loss | Highest dv/dt and switching energy for a given output ripple | Lower voltage steps and filter burden; high-frequency commutation can be assigned to SiC devices | Can distribute loss and use redundant states; ANPC permits active loss balancing |
| Conduction loss | Fewest devices in current path | Some states add series devices; T path can be efficient near unity power factor | More clamping paths/devices; conduction can exceed T-type unless optimized |
| Neutral-point balance | No split-link midpoint control | Requires midpoint sensing, redundant-state selection, capacitor sizing, and modulation limits | NPC/ANPC offers more redundant states; ANPC gives the best active balancing flexibility |
| Common-mode / EMI | Largest voltage steps and common-mode excitation | Reduced step magnitude; still requires CM choke, shield/capacitor strategy, leakage-current study | Potentially best CM shaping, but switching-state complexity is higher |
| Magnetics / filter | Largest LCL/filter volume at equal ripple target | Smaller differential filter is plausible at 50 kHz | Similar or slightly better than T-type depending modulation |
| Control complexity | Lowest | Moderate-high: midpoint balance, dead time, state constraints | Highest: redundant state and loss-balancing optimization |
| Fault behavior | Simple state set, but full bus appears across devices | Midpoint capacitor imbalance and clamping-path faults must be detected; safe commutation is nontrivial | More devices/failure combinations; ANPC can isolate some stress but validation burden rises |
| Module availability | Broad half-bridge and six-pack supply | Documented three-level modules exist; custom discrete assemblies also possible | NPC/ANPC modules available but exact pinout/topology limits sourcing |
| Recommendation | Reference/control-study fallback | Selected baseline for detailed simulation and lab prototype | Retain as alternate if midpoint balance, thermal sharing, or CM results favor ANPC |
Table
| Port | Non-isolated interleaved boost/buck direction | Isolated CLLC direction | Isolated DAB direction |
|---|---|---|---|
| PV | Interleaved boost is lowest part count and efficient when PV string remains safely below bus; no galvanic isolation | Resonant isolation is attractive for narrow conversion ratio and soft switching but MPPT envelope complicates gain range | Bidirectionality unnecessary for PV; DAB adds cost unless isolation policy dominates |
| Battery | Interleaved bidirectional buck/boost is compact but ties battery insulation/leakage strategy to common bus | CLLC can provide high efficiency near design ratio; bidirectional control and wide battery SoC range are challenging | Strong candidate for wide-range bidirectional isolation, controllable power flow, and fault segmentation; circulating current at light load must be managed |
| Misc DC | Interleaved bidirectional is preferred if external port is already isolated/listed | CLLC if port has bounded voltage ratio and isolation is mandatory | DAB if wide-range bidirectional operation and galvanic separation are product requirements |
Table
| Operating point | Line RMS current | Sinusoidal peak |
|---|---|---|
| 20 kW | 83.3 A | 118 A |
| 25 kW | 104.2 A | 147 A |
| 30 kW | 125.0 A | 177 A |
| 40 kVA surge | 166.7 A | 236 A |
| 50 kVA surge | 208.3 A | 295 A |
Table
| Function | Candidate family/class | Reason / qualification needed |
|---|---|---|
| 1200 V SiC module | Wolfspeed XM3 half-bridge, e.g. CAB400M12XM3 / CAB450M12XM3 | Active 1200 V low-inductance module family; size is likely excessive for each switch position unless paralleled topology/module mapping is optimized. Wolfspeed CAB450M12XM3 |
| 3-level SiC module | Infineon CoolSiC EasyPACK F3L3MR12W3M1H_H11 | Documented 1200 V, 200 A nominal, 400 A repetitive, three-level ESS-oriented module; strong topology-specific candidate. Infineon datasheet |
| Discrete SiC | Infineon 1200 V CoolSiC MOSFET family; Wolfspeed 1200 V discrete portfolio | Supports loss/parallel-layout comparison; discrete current sharing, source inductance, creepage, assembly yield, and serviceability are major risks. Infineon 1200 V family |
| Gate driver | TI UCC21750 / UCC21750-Q1 reinforced isolated smart driver | Reinforced isolation, ±10 A drive, DESAT, Miller clamp, soft turn-off features; daughtercard must demonstrate CMTI above 100 kV/µs and system false-trigger immunity. TI UCC21750 |
| Current sensing | LEM HLSR/HASS closed-loop or fluxgate families; TI TMCS1123 reinforced Hall-effect family for lower-current branches | Use isolated sensors for converter/source current plus separate service CT path. Final choice requires bandwidth, offset drift, isolation working voltage, aperture/conductor thermal, and saturation recovery data. LEM current transducers · TI TMCS1123 |
| DC-link film capacitors | TDK B3277* DC-link polypropylene family | 900–1200 V class variants, high ripple capability; bank design must use RMS ripple, hotspot, lifetime, ESL, discharge, and fault-energy calculations. TDK DC-link family |
| HV DC contactors | Littelfuse DCNHE100 / DCNHF60 families | Active 1000 V DC contactor classes; interrupt capability, polarity, economizer, auxiliary feedback, coil suppression, and fuse coordination must match each port. DCNHE100 |
Preserved Baseline
Grid-Stage Topology Comparison
DC/DC Direction Study
Electrical Stress Assumptions
Candidate Component Families
Module vs Discrete
Required Simulation and Lab Gates
Recommendation and Unresolved Decisions